BlockĆTransfer Write

You can generate all block-transfer writes to your 1771-TCM module thru
a single block-transfer write instruction. Enter the block length as 64
words. Write your ladder logic so that when you want to send a particular
block of data to the 1771-TCM module, you first send it to the 64-word
block addressed by the BTW instruction and then use the BTW instruction
to send it to the module.

Configuration Block for Loop 2

23 words

Configuration Block for Loop 1

23 words

Configuration Block for Loop 3

23 words

Configuration Block for Loop 4

23 words

Configuration Block for Loop 5

23 words

Configuration Block for Loop 6

23 words

Configuration Block for Loop 7

23 words

Configuration Block for Loop 8

23 words

Gains Block

57 words

Calibration Write Block

20 words

64Ćword block

addressed by the

blockĆtransfer

write instruction

Dynamic Block

34 words

1771ĆTCM Module

PLC Data Table

BlockĆtransfer Write

Step 1 Ċ

You first send a particular

block of data it to the 64Ćword

block addressed by the BTW

instruction.

Step 2 Ċ

You then use the

BTW instruction to

send the block of

data to the module.

At the beginning of each block is a block identification code that you use
to tell the module which block it is. The module automatically uses only
the number of words appropriate for that particular type of block.