Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual
Page 49

Operating the Module
Chapter 6
6-6
Word Description
Bits
24
0-15
LoopĆ6 Run Temperature SetĆpoint Value Ċ Used when bit 2 of word 2
2
is on (0 thru 999.9
).
25
0-15
LoopĆ6 Manual Output Value (CV) Ċ Used when bit 1 of word 22 is off (-100.00 thru +100.00).
26
0
LoopĆ7 Enable
•
0 = Loop 7 disabled.
•
1 = Loop 7 enabled if PID control mode selected (bits 7-8, word 2, config block).
1
LoopĆ7 Auto/Manual Mode Select
•
0 = Loop 7 is in the manual mode Ċ the manual output value (from word 29) is used as the CV value.
•
1 = Loop 7 is in the automatic mode Ċ the PID algorithm generates the CV value.
2
LoopĆ7 SetĆPoint Select
•
0 = Select the standbyĆtemperature setĆpoint value from word 27.
•
1 = Select the runĆtemperature setĆpoint value from word 28.
3
LoopĆ7 AutoĆTuning Enable
•
0 = Disable autoĆtuning.
•
1 = Enable autoĆtuning Ċ autoĆtuning can be invoked by an offĆtoĆon transition of bit 1 of word 34.
4
Always = 0.
5
LoopĆ7 PID Integral Term Reset Enable
•
0 = Accumulate PID integral term.
•
1 = Reset the PID integral term on the 0ĆtoĆ1 transition, and then allow accumulation until the next 0ĆtoĆ1 transition.
6-15
Always = 0.
27
0-15
LoopĆ7 Standby Temperature SetĆpoint Value Ċ Used when bit 2 of word 26 is off (0 thru 999.9
).
28
0-15
LoopĆ7 Run Temperature SetĆpoint Value Ċ Used when bit 2 of word 26 is on (0 thru 999.9
).
29
0-15
LoopĆ7 Manual Output Value (CV) Ċ Used when bit 1 of word 26 is off (-100.00 thru +100.00).