Dynamic block – Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual
Page 45

Operating the Module
Chapter 6
6-2
The dynamic block contains 34 words as follows:
Words 1 thru 34 of the dynamic block are identified by the mnemonics
TDC01 thru TDC34 in ProSet 700 software.
Word Bits
Description
1
0-15
Block Identification Code Ċ 1000 1000 0000 1010 (880A
16
)
2
0
LoopĆ1 Enable
•
0 = Loop 1 disabled.
•
1 = Loop 1 enabled if PID control mode selected (bits 7-8, word 2, config block).
1
LoopĆ1 Auto/Manual Mode Select
•
0 = Loop 1 is in the manual mode Ċ the manual output value (from word 5) is used as the CV value.
•
1 = Loop 1 is in the automatic mode Ċ the PID algorithm generates the CV value.
2
LoopĆ1 SetĆPoint Select
•
0 = Select the standbyĆtemperature setĆpoint value from word 3.
•
1 = Select the runĆtemperature setĆpoint value from word 4.
3
LoopĆ1 AutoĆTuning Enable
•
0 = Disable autoĆtuning.
•
1 = Enable autoĆtuning Ċ autoĆtuning can be invoked by an offĆtoĆon transition of bit 1 of word 34.
4
Always = 0.
5
LoopĆ1 PID Integral Term Reset Enable
•
0 = Accumulate PID integral term.
•
1 = Reset the PID integral term on the 0ĆtoĆ1 transition, and then allow accumulation until the next 0ĆtoĆ1 transition.
6-15
Not used.
3
0-15
LoopĆ1 Standby Temperature SetĆpoint Value Ċ Used when bit 2 of word 2 is off (0 thru 999.9
).
4
0-15
LoopĆ1 Run Temperature SetĆpoint Value Ċ Used when bit 2 of word 2 is on (0 thru 999.9
).
5
0-15
LoopĆ1 Manual Output Value (CV) Ċ Used when bit 1 of word 2 is off (-100.00 thru +100.00).
Dynamic Block