User-defined scaling data format to real units – Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual
Page 63
Publication 1746-UM001A-US-P
Channel Configuration, Data, and Status 5-15
1746-NI4 Data Format Units to Real Units
Example: #5 A transducer is being used to measure flow rate.
The -10V dc to +10V dc signal range is proportional to 0 to 100 GPM
The input data is in “1746-NI4” format, i.e. input range of -32768 to 32767
Input value to convert = 10000
The Scaled range is 0 to 100 GPM
The Input range is -32768 to +32767
Find: Input value in GPM
Per the equations above:
User-Defined Scaling Data Format to Real Units
Example: #6 A transducer is being used to measure pressure.
The -10V dc to +10V dc signal range is proportional to 0 to 200 psi
The input data is in “User Defined Format”, where:
The lower input limit (configuration word 8) = 0
The upper input limit (configuration word 9) = 20000
Input value to convert = 16600
Scaled range is 0 to 200 psi
Input range is 0 to 20000
Find: Input value in psi
Per the equation above:
Slope
100
0
–
(
)
32767
32768
–
(
)
–
[
]
------------------------------------------------------
0.0015
=
=
Offset
0
32768
–
0.0015
×
(
)
49.15
=
–
=
Scaled Value
10000
0.0015
×
(
)
49.15
64.15 GPM
=
+
=
Slope
200
0
–
(
)
20000
0
–
(
)
--------------------------------
0.01
=
=
Offset
0
0
0.01
×
(
)
0
=
–
=
Scaled Value
16600
0.01
166 psi
=