Output image channel configuration procedure, Output image channel configuration procedure -2 – Rockwell Automation 1746-NI16V SLC 500 Analog Input Modules User Manual User Manual
Page 50
![background image](/manuals/579568/50/background.png)
Publication 1746-UM001A-US-P
5-2 Channel Configuration, Data, and Status
After installation, each channel must be configured to establish the
way the channel operates. You configure the channel by entering bit
values into the configuration word using your programming device. A
bit-by-bit examination of the configuration word is provided in the
chart on page 5-3. Programming is discussed in Chapter 7. Addressing
is explained in Chapter 4.
The configuration word default setting is all zeros.
Output Image Channel
Configuration Procedure
The channel configuration word consists of bit fields, the settings of
which determine how the channel operates. See the chart on the
following page and the descriptions that follow for configuration
information. Appendix B contains a configuration worksheet.
After determining the configuration for each channel, follow the steps
outlined in Chapter 2, Quick Start, or in Chapter 7, Application
Examples, to enter this configuration data into your ladder program
and copy it to the 1746-NI16 module.