Chapter summary, Controlnet status indicators – Rockwell Automation 1771-ACNR15 CONTROLNET ADAPTER MODUL User Manual

Page 45

background image

5–3

Publication 1771-6.5.124 – August 1997

Recommended Action

Probable Cause

Description

Display

Mnemonic

STATUS

NET

ADDRESS

OK Indicator

OK

Red/
Green

Recommended Action

Probable Cause

Description

Display

Mnemonic

STATUS

NET

ADDRESS

OK Indicator

OK

Red/
Green

Green

RUN

Normal indication – processor is in
RUN mode.

None

None

PRGM

Normal indication – processor is in
program or test mode.

None

None

Blinking
alternately red
and green

BOOT

Running boot code.

Adapter has corrupted firmware.

Update adapter firmware with A-B
Flash Update Utility.

ControlNet Status Indicators

steady

indicator is on continuously in the defined state.

alternating – the two indicators alternate between the two defined states at the
same time (applies to both indicators viewed together). The two indicators are
always in opposite states, out of phase.

flashing – the indicator alternates between the two defined states (applies to
each indicator viewed independent of the other). If both indicators are
flashing, they must flash together, in phase.

A

B

and

Cause

Action

Off

No power

None or power up

Steady red

Faulted unit

Cycle power or reset unit

If fault persists, contact A-B representative or distributor.

Alternating red/green

Self-test

None

Alternating red/off

Incorrect node configuration

Check network address and other ControlNet configuration
parameters

A

B

or

Cause

Action

Off

Channel disabled

Program network for redundant media, if required

Steady green

Normal operation

None

Flashing green/off

Temporary errors

None; unit will self-correct

las ing g

n o

Node is not configured to go on
line

Make sure the configuration manager node is present and
working➀

Flashing red/off

Media fault

Check media for broken cables, loose connectors, missing
terminators, etc.

No other nodes present on
network

Add other nodes to the network

Flashing red/green

Incorrect network configuration

Cycle power or reset unit

If fault persists, contact A-B representative or distributor.

➀ The configuration manager node is the node responsible for distributing ControlNet configuration data to all nodes on the network.

In this chapter you learned how to use the indicators on the front of
the module to troubleshoot your module.

Chapter Summary