Rockwell Automation 1771-ACNR15 CONTROLNET ADAPTER MODUL User Manual

Page 32

background image

3–8

Addressing Modes for Your I/O

Publication 1771-6.5.124 – August 1997

When the 1771-ACN15/ACNR15 ControlNet adapter module
addresses a 1-slot I/O group containing a 32-point I/O module, the
adapter module uses the unused word assigned to the adjacent I/O
module slot. For example, the adapter module uses the unused input
word associated with I/O slot 1 (because that slot must hold an
output module and does not use its input word).

Figure 3.7 illustrates the concept of 1-slot addressing with two
32-point I/O modules.

Figure 3.7
1-slot I/O Group Concept With 32-point I/O Modules

3 2 –p o in t I/O M o d ules

In pu t W o rd 0

O u tp u t W o rd 0

Im a g e T a b le
W ord s A llo ca te d
fo r I/O G ro u p 0

In pu t W o rd 1

O u tp u t W o rd 1

Im a g e T a b le
W ord s A llo ca te d
fo r I/O G ro u p 1

S lo t 0

Inp u t M o d u le

I/O G ro u p 0

S lo t 1

O u tp u t M o d u le

I/O G rou p 1

14 25 8