Double-word – Rockwell Automation 1746-MPM INSTALL INSTRUC MOLD PRESSURE User Manual
Page 18
18
Mold Pressure Module
Publication 1746-5.13 July 1998
Summary data notes
Single-word
summary values are stored with bytes reversed. You must use
the Swap instruction to convert them to integer format.
Double-word
summary values are stored as integer pairs, with the low-
word value stored in the lower address of the pair, high-word value in upper.
12. Specifications
Description:
Value:
electrical
backplane current
backplane power
number of input channels
A/D conversion
common-mode rejection
dynamic response
0.3A @ 5V dc
1.5W
2
12-bit successive approximation
115 do @ 500 gain
200K Hz @ 500 gain
sensor inputs
input types lo-level
input types hi-level
gain settings
sensor excitation voltage
sensor excitation current
isolation from backplane
2, 6, and 9 mV/V strain gage
4-20mA self-powered
0-10V dc
1, 100, 250, 450
10.000V dc ±0.002V dc
35mA per channel
1500V rms
mechanical
module ID
number of LED indicators
cable for channels
cable for DartNets
12935
4 (alarm condition and module status)
Belden 8102
Belden 9462
temperature
operating
storage
0° to 60° C
(32 to 140° F)
-40° to 85° C
(-40 to 185° F)
relative humidity
5% to 95% noncondensing
agency certification
1
(when product or packaging is marked)
1.
CSA certification - Class I Division 2, Group A, B, C, D or nonhazardous locations
FM approved - Class I, Division 2, Group A, B, C, D or nonhazardous locations
Class I Division 2 Hazardous
marked for all applicable directives