Fault Codes

Chapter 10

10-3

Motor Stalled

Freq

P

R

Indicates that the drive has not been able to change output frequency for 4
seconds.

Conditions sensed are:

Excessive Current

The motor is drawing excessive current (over 115%). The motor load is
excessive and will not allow the drive to accelerate to set speed. A longer
accel time or a reduced load may be required.

Bus Voltage Rise

The bus voltage has risen to 110% of nominal bus voltage. This indicates a
regeneration condition that will not let the drive decelerate to a lower
frequency. A longer decel time or dynamic braking may be required.

Motor Overload

Freq

P

R

The drive output current has exceeded the % of current set by Overload
Current Parameter 38 for some period of time. The time is dependent on
the level of current above the set value. The fastest time is 115% of
Parameter 38 for one minute. This indicates an excessive motor load that
must be reduced to the value programmed by Parameter 38.

Over Temperature

Freq

P

R

Drive logic has detected an open temperature switch on the drive heatsink
indicating that drive heatsink temperature is above 100

°

C. Check for

blocked or dirty heatsink fins. Check that the ambient temperature has not
exceeded 40

°

C. For 14 Amp and larger units, check the operation of the

drive cooling fan.