Motor stalled, Motor overload, Over temperature – Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual
Page 91
Fault Codes
Chapter 10
10-3
Motor Stalled
Freq
P
R
Indicates that the drive has not been able to change output frequency for 4
seconds.
Conditions sensed are:
Excessive Current
The motor is drawing excessive current (over 115%). The motor load is
excessive and will not allow the drive to accelerate to set speed. A longer
accel time or a reduced load may be required.
Bus Voltage Rise
The bus voltage has risen to 110% of nominal bus voltage. This indicates a
regeneration condition that will not let the drive decelerate to a lower
frequency. A longer decel time or dynamic braking may be required.
Motor Overload
Freq
P
R
The drive output current has exceeded the % of current set by Overload
Current Parameter 38 for some period of time. The time is dependent on
the level of current above the set value. The fastest time is 115% of
Parameter 38 for one minute. This indicates an excessive motor load that
must be reduced to the value programmed by Parameter 38.
Over Temperature
Freq
P
R
Drive logic has detected an open temperature switch on the drive heatsink
indicating that drive heatsink temperature is above 100
°
C. Check for
blocked or dirty heatsink fins. Check that the ambient temperature has not
exceeded 40
°
C. For 14 Amp and larger units, check the operation of the
drive cooling fan.