Terminal Block TB2
The drive is capable of operating from an optional Local or Remote
Control and Signal Wiring
Control Panel with minimum connections to terminal block TB2. When
required, external operator elements may be connected to provide
additional drive control. Additional drive control functions and status
outputs are also available for use at TB2 as detailed on the following pages.
Pot
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Wiper
Pot
High
Pot
Low
External
Speed Pot
+
–
+
–
+
–
+
–
CR1
CR2
CR3
CR3
CR4
CR4
ISOL
Analog
Meter
0–10V
Pulse
Source
4–20mA
At
Fault
(Not)
Drive
(Not)
Run
Speed
Fault
Alarm
Drive
Alarm
Shield
To
Pulse
Input
Fro
m
D/A
To
A/D
2
To
A/D
3
To
A/D
1
+5V
DC
1.4k
Ω
215
Ω
215
Ω
100
Ω
100
Ω
47.5k
Ω
200
Ω
49.9Ω
53.3k
Ω
75k
Ω
100
Ω
3.42k
Ω
Chassis
Ground
Signal
Common
Maximum
Recommended
Signal
Wire Group ❶
Wire Size ❷
Torque ❸
Terminals 1, 2, 3
External Speed Potentiometer
5
14 AWG
7 In-Lbs
Terminals 3 and 4
Signal Common
5
14 AWG
7 In-Lbs
Terminals 5, Signal Common
0-10V DC
5
14 AWG
7 In-Lbs
Terminals 6, Signal Common
4-20mA
5
14 AWG
7 In-Lbs
Terminals 7 and 8
Pulse Train
6
14 AWG
7 In-Lbs
Terminals 9, Signal Common
Meter Output
5
14 AWG
7 In-Lbs
Terminals 10 and 11
At Speed Contact
3
14 AWG
7 In-Lbs
Terminals 11 and 12
Run Contact
3
14 AWG
7 In-Lbs
Terminals 13, 14, 15
Fault Contacts
3
14 AWG
7 In-Lbs
Terminals 16, 17, 18
Drive Alarm Contacts
3
14 AWG
7 In-Lbs
❶ Wire group number chart, page 6-3.
❷ 2.50 mm
2
.
❸ .79 N-m.