Step 15ăauxiliary interlock check, Step 16ăjog check, Step 17ăskip frequencies – Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual
Page 83
Startup
Chapter 9
9-8
Initial Operation
Step 14
- Motor Disconnected (cont.)
Freq
P
R
While the drive is running, open the Enable Signal at TB3, Terminal 30.
The drive will stop and display the Enable Lost Code – – – - -.
Restore the enable signal.
Step 15ăAuxiliary Interlock Check
Start
Restart the drive. With the drive running, open the auxiliary interlock
signal at TB3, Terminal 28. The drive will stop and display the Enable
Fault F02 – –.
Freq
P
R
Stop
Stop
Restore the auxiliary signal and reset the drive by pressing the Stop
pushbutton twice.
Step 16ăJog Check
Jog
With the drive reset but not running, press and hold the Jog pushbutton on
the Control Panel.
If the Jog function is active (Parameter 23 = 1), the drive will start and
ramp to jog speed.
If the Jog function is not active (Parameter 23 = 0), the drive will not start.
Step 17ăSkip Frequencies
Start
Start the drive and slowly progress through the drive frequency range by
turning the Control Panel speed pot clockwise.
If skip frequencies are programmed, verify that the drive cannot be set to a
skip frequency but will remain above or below the skip frequency as set by
the Skip frequency range.
If skip frequencies are not programmed, verify that the drive will not skip
any frequencies in the drive operating range.