beautypg.com

Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual

Page 115

background image

Logic Interface Options

Appendix A

A-17

1336ĆMODĆL3 115V AC

Terminal 20 and Interface Common

Logic Interface Board

(This signal must be maintained as True to permit the drive to operate from any
control source.)

Stop

Maintained True = Not Stop

Momentary False = Stop

Stop must be a maintained True input to permit the drive to start and run. A
momentary False of 90mS or more or any other drive stop command will
initiate a drive stop sequence as programmed by Parameter 10, Stop Select.

Terminals 21, 25, 29

Interface Common

Terminals 21, 25 and 29 are used to terminate both minus or interface
common signals to TB3. Terminals 21, 25 and 29 are also used to terminate
any shields for cables connected to TB3. For the 1336-MOD-L3 115V AC
Logic Interface Board, Terminals 21, 25 and 29 are isolated from drive
signal common, chassis ground, and earth ground.

Terminal 22 and Interface Common

Jog

True = Jog

False = Interrupt Jog and Allow Other Functions

This input will jog the drive if it is not running and interlocks permit. As
long as interlocks permit and the jog command remains True, the drive will
continue to run at the programmed jog frequency.

Terminal 23 and Interface Common

Reverse

Maintained True = Reverse

Maintained False = Forward

Parameter 22 enables the direction of drive rotation to be controlled by an
input at Terminal 23. A maintained False will select the forward direction,
a maintained true the reverse direction.