Rockwell Automation 1336VT 5-300 AMP (2.2-160KW) User Manual
Page 32
Specifications
Chapter 4
4-5
Output Power (cont.)
Boost:
11 selectable values from 0 to 48V DC peak.
– Adjustable from 0 to 115V DC through optional
programming.
– Independent Accel/Run Boost to minimize motor
heating while maximixing motor torque.
Accel/Decel:
Two independently programmable accel times.
Two independently programmable decel times.
Each time may be programmed over a range from
0 to 600 seconds.
Intermittent
Programmable MOPC from 50 to 115% of rated output
Overload Capability: current for up to 1 minute maximum.
Inverse Time
Designed to meet NEC and UL equivalent requirements.
Overload Capability: Adjustable timing from 50 to 115% of rated drive current
(Main Control Board Firmware Version 1.10 limited to 100%).
Drive
180% of rated output current.
Overcurrent Trip:
Ground Fault:
Detects drive output ground fault path by sensing
unbalanced bus or input line currents.
Table 4.4 Ċ 1336VT Output Current and kVA
Internal
Chassis
Component
Heatsink
Heat
Heat
Total
Minimum
Drive
kVA Out
kVA Out
kVA Out
Dissipation
Dissipation
Dissipation
CFM
Amps Out
Rating
380V AC
415V AC
460V AC
(BTU/hour) n
(BTU/hour) n
(BTU/hour) n
Required n
5.0
B003
3.3
3.6
4.0
119
171
290
15
8.0
B005
5.3
5.8
6.4
154
222
375
20
11.0
B007
7.2
7.9
8.8
239
375
614
32
14.0
B010
9.2
10.1
11.2
290
460
750
40
21.0
B015
13.8
15.1
16.7
409
1040
1449
75
27.0
B020
17.8
19.4
21.5
477
1228
1705
88
34.0
B025
22.4
24.4
27.1
495
1449
1944
100
40.0
B030
26.3
28.8
31.9
597
1620
2217
115
52.0
B040
34.2
37.4
41.4
767
2404
3171
165
65.0
B050
42.8
46.7
51.8
1006
2882
3887
200
77.0
B060
50.7
55.3
61.3
1159
3001
4160
215
96.0
B075
63.2
69.0
76.5
1398
3274
4672
241
124.0
B100
81.6
89.1
98.8
1773
5456
7229
375
156.0
B125
102.7
112.1
124.3
2114
8116
10230
527
180.0
B150
118.5
129.4
143.4
2387
8184
10571
545
240.0
B200
158.0
172.5
191.2
2933
12753
15686
810
300.0
B250
197.4
215.6
239.0
3171
14902
18073
932
n The above information is provided for reference only. For all ratings the user must verify that the selected enclosure will dissipate the total BTUs
generated within the enclosure without allowing the internal ambient to rise above 50
°
C. Enclosure mounting and location must allow for the heatsink
to extend outside the enclosure.
•
When locating the drive allow a minimum clearance from other components of 4.0 inches (101.6 mm) on the top and bottom, 2.0 inches (50.8 mm) on
either side.
•
When mounting the drive, ensure that the heatsink fins are vertical.
With the heatsink exposed to the ambient, the drive will dissipate heat as listed in the Output Current Table above.