Fault Codes

Chapter 10

10-2

Auxiliary Fault

Freq

P

R

The auxiliary input interlock is open. The auxiliary interlock is:

Jumper 9-10 of J9 on the Main Control Board if interface option L1, L2,
L3 is not installed.

Terminal 28 of TB3 if interface option L1, L2 L3 is installed.

Power Loss

Freq

P

R

Occurs only if Parameter 40 is set to 0 and input power is interrupted for
0.2 seconds. Monitor the incoming AC line for low voltage or line power
interruption.

Bus Undervoltage

Freq

P

R

Occurs when the DC bus drops below 388V DC.

Monitor the incoming AC line for low voltage or line power interruptions.

Bus Overvoltage

Freq

P

R

Occurs when the DC bus rises above 810V DC.

May be caused by high line voltage or excessive regeneration from the
motor. Monitor the AC line for high line voltage or transient conditions. If
caused by motor regeneration, extended decel time or dynamic braking
may be required.