Rockwell Automation 1302 575v AC Drive - Canada Only User Manual
Page 72
8–14
Programming
Publication 1302-5.0 — January, 1998
FĆ18 RPM Setpoint Enable
The parameter enables the
setpoint to be displayed in FĆ08
units.
Parameter Range:
Default Setting:
Step Size:
OFF = Setpoint is displayed in hertz.
ON = Setpoint is displayed in the units
specified in FĆ08.
ON
N/A
If FĆ18 = ON, pressing the
and
keys will change the setpoint in units of 1 between minimum
speed in FĆ08 units and maximum speed in FĆ08 units. Note that this parameter only affects the setpoint, not
the display.
Example
Assume a Drive is currently running at 60 Hz = 1750 RPM, FĆ08 = 1750, and FĆ10 = ON. When the
key is pressed, 1750 is displayed. When the
key is pressed three more times, the display will change
from 1750 to 1749 to 1748 to 1747. The reference is then rescaled based on this input:
Input reference +
Reference (1747)
FĆ08Ă(1750)
FĆ04Ă(60Hz) + 59.89 Hz
FĆ19 PowerĆUp Start Enable
This parameter determines
whether the motor starts
automatically when the Drive is
powered up.
Parameter Range:
Default Setting:
Step Size:
OFF = Motor does not start at Drive
power up.
ON = Motor starts at Drive power up.
OFF
N/A
!
ATTENTION: Setting FĆ19 = ON causes output power to be applied to the motor automatically
at Drive power up. When this function is enabled, you must ensure that automatic start up of the
driven equipment will not cause injury to operating personnel or damage to the driven
equipment. In addition, you are responsible for providing suitable audible or visual alarms or
other devices to indicate that this function is enabled and the Drive may start at any moment.
This parameter may only be used as outlined in NFPA79, paragraph 6-14 (exceptions 1-3) for
specialized applications. Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application.
When FĆ19 = ON, output power is applied to the motor at drive power up if the following conditions are met:
D The drive powerĆup diagnostics must be passed (SELF will be displayed at power up).
D No faults can be active.
D The terminal strip function loss input must be closed.
D The frontĆpanel keypad
STOP
RESET
key must not be pressed.
If the Drive is under local control, it will effectively simulate a start signal to start the Drive.
If the Drive is under remote control, the Drive will start only if the terminal strip START input is asserted.