Program security, Step 5 .press the or key to change the value, Key to save the changed value – Rockwell Automation 1302 575v AC Drive - Canada Only User Manual
Page 60: Press the, 8–2 programming
![background image](/manuals/578192/60/background.png)
8–2
Programming
Publication 1302-5.0 — January, 1998
Step 5 .Press the
or
key to change the value.
Mode
Enter
START
Forward
Reverse
STOP
RESET
RPM
%Load
Volts
Remote
RUN
Program
Forward
Reverse
Note that if programming has been disabled in parameter F-20
(Password Lockout Enable), the value will not change. Refer to
Chapter 8, Ensuring Program Security, for more information.
Step 6.
Press the
Mode
Enter
key to save the changed value.
Mode
Enter
START
Forward
Reverse
STOP
RESET
RPM
%Load
Volts
Remote
RUN
Program
Forward
Reverse
The parameter number is displayed again.
To display or change additional parameters, repeat steps 3
through 6.
To exit program mode, press the
Mode
Enter
key until a parameter
number or ERR is displayed; then press the
STOP
RESET
key.
Important: Parameter values and the keypad status (local or
remote) are retained through a line dip or power loss.
!
ATTENTION: It is your responsibility to determine how
to distribute the password. Allen–Bradley is not
responsible for unauthorized access violations within the
user’s organization. Failure to observe this precaution
could result in equipment damage or bodily injury.
Parameter values can be password-protected using parameter F-20
(Password Lockout Enable). When F-20 is set to ON, parameter
values can be displayed but cannot be modified from the keypad
unless the correct password is entered in F-20.
Note: The password is factory set to 257 and cannot be modified by
the user.
Program Security