1302 AC Drive Description
This chapter describes the 1302 Drive and how to identify it based
on its model number. This chapter also provides power and
enclosure rating information.
The 1302 Drive has the following features:
•
On-board keypad and display providing:
Start/Stop/Reset control
Forward/Reverse (reverse-disable selectable)
Setpoint adjustment, Motor RPM, %load, or output voltage
display
Drive diagnostics
•
500 millisecond power dip ride-through
•
150% overload for one minute
•
0.5 to 240 Hz three-phase voltage output
•
NEMA 1 and NEMA 4/12 enclosures
•
A snubber resistor braking signal and a scaled voltage analog
output (0 to 10 VDC) which is proportional to:
Output frequency
Output amps
Output voltage
Selected reference
•
Quiet motor operation with high carrier frequency selection
•
Drive protection:
Overcurrent
Short circuit
Ground fault
Overvoltage
Undervoltage
Overtemperature
•
UL/CSA electronic overload that meets NEC/CEC requirements
•
User-selectable relay contact for indications of Drive running,
Drive faulted, or Drive at selected speed
•
User-selectable power-up start, auto-restart, and coast-to-rest or
ramp-to-rest stop functions
•
User-selectable local or remote operation
•
29 user–adjustable software parameters
Introduction
Standard Features