Parameter descriptions, Step 5. press the, Key to exit the parameter – Rockwell Automation 1302 575v AC Drive - Canada Only User Manual
Page 62

8–4
Programming
Publication 1302-5.0 — January, 1998
Step 5. Press the
Mode
Enter
key to exit the parameter.
Mode
Enter
START
Forward
Reverse
STOP
RESET
RPM
%Load
Volts
Remote
RUN
Program
Forward
Reverse
Important:
There is no visual indication of the status of this
feature. You must access F-20 to verify its current
value (ON or OFF
).
Displaying or Changing Parameter Values
FĆ00 Control Source Select
This parameter selects the Drive
control source and speed
reference source.
Parameter Range:
Default Setting:
Step Size:
0 = Local control; control signals and
speed reference from the keypad
1 = Remote control; control signals from
the terminal strip; speed reference
from the analog input
2 = Remote control; control signals from
the terminal strip; speed reference
from the keypad
3 = Remote control; control signals from
the terminal strip; multiĆspeed presets
from the terminal strip
0 = Local control
N/A
When FĆ00 = 0, the Drive responds to sequencing commands (start, stop, forward, reverse) from only
the keypad.
When FĆ00 = 1, 2, or 3, the Drive responds to sequencing commands from the terminal strip. Note that
the drive will respond to the stop command from the keypad regardless of the value in this parameter.
Refer to the FĆ23 to FĆ25 MultiĆSpeed Presets parameter description for more information about
multiĆspeed presets.
Parameter Descriptions