WI-I/O 9-L Configuration Manual

WI-I/O 9-L Wireless I/O

page 80 of 108

7. Enter the new value:

Fill the cold-junction table with the millivolt output of the thermocouple corresponding to each

10-degree temperature increment. Your thermocouple documentation should contain this

information.
The Linearization table lets you enter up to 51 data points relating the thermocouple voltage

to the desired output value.
You can enter the desired output value either as a milliamp value (range 0-20 mA) or as a

raw 16-bit unsigned value. Refer to Appendix A – Tables for translating different analog signal

types on page 104 for more information.

Note

You must enter the millivolt input values in ascending order; with the lowest millivolt
value entered into entry 1, and the highest in the last used entry.

Unused entries should be set to “100” millivolts.

8. WI Series writes the new thermocouple tables and settings to the module when you next

configure the module.