Unit sensitivities indicate the change required in an analog input for the WI-I/O 9-L-T to detect
a state change and trigger any mapping that includes the input.
If you set the sensitivity to a small value, the mappings using the input will trigger on a small
change of value. If the input is noisy or variable, this can congest the radio channel by
sending multiple spurious messages. You can overcome this situation by increasing the
sensitivity value.
To set unit sensitivities:
1. Open the project.
2. Select the unit you want to change.
3. Select
Sensitivities
4. WI Series shows the sensitivities for the unit:
5. Select the sensitivity you want to change and click
Edit Sensitivities
.
6. WI Series shows the sensitivity:
7. Set the sensitivity as required and click
OK
to set the new value or click
Cancel
to return to the sensitivity list without changing the sensitivity.
8. WI Series will write the new sensitivity value to the module when you reconfigure it.
- ACT20X (182 pages)
- ACT20X-HDI-SDO: NAMUR pulse isolator (2 pages)
- ACT20X-SDI-HDO: Solenoid/Alarm driver (2 pages)
- G108 Ultra SlimPak (4 pages)
- G118 Ultra SlimPak (4 pages)
- G128 Ultra SlimPak (4 pages)
- G168 Ultra SlimPak (4 pages)
- G408 Ultra SlimPak (4 pages)
- G408-1000 Ultra SlimPak (4 pages)
- G418 Ultra SlimPak (4 pages)
- G428 Ultra SlimPak (4 pages)
- G438 Ultra SlimPak (4 pages)
- G448 Ultra SlimPak (4 pages)
- G468 Ultra SlimPak (4 pages)
- G478 Ultra SlimPak (4 pages)
- HS01 Heat Sink (Ultra SlimPak series) (2 pages)
- WAVE Analog 2 OLP (7 pages)
- WAVE Analog DC/DC (7 pages)
- WAVE Analog DC Alarm (10 pages)
- WAVE Analog OLP (7 pages)
- WAVE Analog PRO Bridge (9 pages)
- WAVE Analog PRO DC (15 pages)
- WAVE Analog PRO Frequency (15 pages)
- WAVE Analog PRO RTD (13 pages)
- WAVE Analog PRO Thermo (13 pages)
- DC/DC CCC DC - with voltage supply on both sides (8 pages)
- DC/DC CCC HF - with 3 way separation (5 pages)
- DC/DC CCC LP - with voltage supply on the output side (8 pages)
- DC/DC CCC LP - without additional voltage supply (8 pages)
- PT 100/2 sig conditioners for current output (14 pages)
- PT 100/2 sig conditioners for voltage output (12 pages)
- PT 100/4 signal conditioners for current output (18 pages)
- PT 100/4 signal conditioners for voltage output (14 pages)
- Thermo Signal Conditioners for current & voltage output (14 pages)
- WAVE Control: Current Monitoring Module (6 pages)
- WAVE Control: VMA Vac Voltage-Monitoring Module (9 pages)
- ITX+ - Universal signal isolator / amplifier (64 pages)
- PMX400TMP - Display instrument for control panel (39 pages)
- PMX420SERIES - Display instrument for control panel (68 pages)
- Portacal 1000 - Instrument Calibrator (41 pages)
- Portacal 275 - Signal source and loop calibrator (32 pages)
- PTX800D - Scalable pulse and frequency counter (22 pages)
- wavePak - Configurable singal isolator-converter (28 pages)
- PU-Overvoltage in Mains Control (4 pages)
- IE-MC-VL Series - Industrial Ethernet Media Converters (14 pages)