Weidmuller WI-I/O 9-L: Wireless I/O Transmitter / Receiver v1.3 User Manual
Page 14

WI-I/O 9-L Configuration Manual
WI-I/O 9-L Wireless I/O
page 14 of 108
This section describes how to configure your WI-I/O 9-L.
Note
For more information on installing your WI-I/O 9-L, please see the
WI-I/O 9-L Installation
Guide
.
You can configure your network using:
User-defined (customized) configuration
– that lets you set specific information
about your network and allows communication with other Weidmuller, Inc. I/O modules.
Default factory configuration
– that lets you use a transmitter and receiver as a
simple send/receive pair.
This manual describes how to perform custom configuration to:
Fully utilize of the features of the WI-I/O 9-L modules; and
Communicate between WI-I/O 9-L modules and other Weidmuller, Inc. I/O modules.
For more information on restoring the default configuration (i.e. linking), refer to the
Quick
Start Guide
included with your module.
The following tables detail the default settings:
Setting
Default
Periodic transmission
Every second
Analog sample rate
5 samples per second
Analog change of state sensitivity
3%
Output state on comms failure
Reset to zero
Analog setpoints
Set by rotary switch (switch value x 10%±5%)
Analog Input debounce
1 sample
Digital input debounce time
0.5 seconds
Signals sent over radio
WI-I/O 9-L-T(Transmitter)
Sends
WI-I/O 9-L-R (Receiver)
Digital Input 1
Digital Output 1
Digital Input 2
Digital Output 2
Analog Setpoint
Digital Output 3
Analog input (4-20 mA)
Analog output