1" n, Scfh, 968 s – Steriflow Mark 968 Series User Manual
Page 4
Set Pressure
Inlet (psi)
Orifice Size
1/8"
3/16"
1/4"
5/16"
3/8"
7/16"
1/2"
9/16"
2" H20
(1-2.5" H20)
1" H20 Droop
2" H20 Boost*
5
226
420
483
630
536
998
1172
1313
10
328
618
702
893
779
1206
1450
20
493
872
1055
1376
803
40
786
1224
1681
2010
60
1073
1447
1872
80
1360
1455
1898
100
1648
1763
150
2146
2256
3" H20
(2-5" H20)
1" H20 Droop
2" H20 Boost*
5
268
419
565
629
689
996
1307
1342
10
356
618
870
892
910
1205
1503
20
469
872
1266
1376
656
40
730
1224
1707
2010
60
963
1447
1926
80
1255
1455
1627
100
1534
1763
150
1981
2256
7" H20
(4-10" H20)
1" H20 Droop
2" H20 Boost*
5
283
378
477
524
565
793
1024
848
10
380
585
791
722
653
1003
1345
20
488
871
1247
1684
2110
2177
35
673
1444
2188
2358
2525
3155
75
1221
2278
3317
90
1399
2623
100
1534
2836
150
1981
3687
28" H20
(5-30" H20)
5-1/2" H20 Droop
5
318
478
636
760
883
991
1095
1130
10
388
613
831
1128
1424
1584
1741
30
373
1074
1756
2192
2608
2834
45
718
1596
2393
2892
60
929
2121
3302
3294
75
1139
2517
100
1449
3219
150
1871
4182
1.25 psi
(0.5 - 1.75 psi)
0.2 psi Droop
5
198
299
482
434
578
511
723
1012
10
267
378
593
608
890
756
1038
964
30
328
552
969
924
1193
1342
45
479
758
1197
1157
1396
60
624
998
1497
1398
1622
75
689
1229
1858
100
920
1609
2376
150
1211
2091
3081
3 psi
(1 - 3.5 psi)
0.3 psi Droop
5
159
238
318
346
371
408
442
742
10
237
355
475
571
672
710
752
831
30
266
550
825
921
1011
1337
45
479
758
1097
1157
1157
60
619
998
1376
1398
1410
75
689
1229
1708
100
852
1609
2387
150
1100
2091
3081
M
ark
968 S
anitary
G
aS
r
eGulator
1" n
2
M
ax
F
low
c
apacity
: scFH
Flow in this area is outside the operating
parameters of the valve
Flow in this area is outside the operating
parameters of the valve
Flow in this area is outside the operating
parameters of the valve
Flow in this area is outside the operating
parameters of the valve
Flow in this area is outside the operating
parameters of the valve
Flow in this area is outside the operating
parameters of the valve
* Boost refers to a small rise in outlet pressure set point that can occur, and is characteristic of, this type of regulator when flow nears the valve's maximum capacity. To understand this
phenomenon and to determine your maximum flow requirements, see API 2000
To select the orifice size for your valve you need to know P1 (inlet pressure). P2 (outlet pressure set point), and maximum flow in SCFH.
1. Select the row that best represents your outlet Set Pressure (P2)
2. Select the sub-row that is representative of your Inlet Pressure (P1)
3. Find the Flow rate in that sub-row that encompasses your maximum flow. Look at the orifice column heading to determine your specific orifice size.
-4-