beautypg.com

3/4" n, Scfh, 968 s – Steriflow Mark 968 Series User Manual

Page 2

background image

Set Pressure

Inlet (psi)

Orifice Size

1/8"

3/16"

1/4"

5/16"

3/8"

7/16"

1/2"

9/16"

2" H20

(1-2.5" H20)

1" H20 Droop

2" H20 Boost*

5

201

374

430

261

477

888

1043

1169

10

213

402

456

580

506

784

943

20

222

392

475

619

361

40

299

465

639

764

60

665

897

1161

80

816

873

1139

100

598

640

150

770

825

3" H20

(2-5" H20)

1" H20 Droop

2" H20 Boost*

5

239

373

503

560

613

886

1163

1195

10

231

402

566

580

591

783

977

20

211

392

570

619

295

40

277

465

649

764

60

597

897

1194

80

753

873

976

100

675

776

150

880

825

7" H20

(4-10" H20)

1" H20 Droop

2" H20 Boost*

5

220

295

372

409

441

619

799

661

10

277

427

578

527

476

732

982

20

258

462

661

893

1118

1154

35

276

592

897

967

1035

1294

75

525

980

1426

90

727

1364

100

813

1503

150

1040

1926

28" H20

(5-30" H20)

5-1/2" H20 Droop

5

302

454

604

722

839

941

1040

1074

10

337

533

723

981

1239

1378

1514

30

283

816

1335

1666

1982

2154

45

617

1373

2058

2487

60

817

1866

2906

2899

75

820

1812

100

840

1867

150

1089

2421

1.25 psi

(0.5 - 1.75 psi)

0.2 psi Droop

5

180

272

439

395

526

465

658

921

10

235

333

522

535

783

665

913

848

30

279

469

824

785

1014

1141

45

354

561

886

856

1033

60

418

669

1003

937

1087

75

427

762

1152

100

543

949

1402

150

715

1266

1816

3 psi

(1 - 3 .5 psi)

0.3 psi Droop

5

145

217

289

315

338

371

402

675

10

209

312

418

502

592

625

661

731

30

226

468

701

783

859

1136

45

354

561

812

856

856

60

415

669

922

937

945

75

427

762

1059

100

503

949

1408

150

660

1266

1816

M

ark

968 S

anitary

G

aS

r

eGulator

3/4" n

2

M

ax

F

low

c

apacity

: scFH

Flow in this area is outside the operating

parameters of the valve

Flow in this area is outside the operating

parameters of the valve

Flow in this area is outside the operating

parameters of the valve

Flow in this area is outside the operating

parameters of the valve

Flow in this area is outside the operating

parameters of the valve

Flow in this area is

outside the operating

parameters of the valve

* Boost refers to a small rise in outlet pressure set point that can occur, and is characteristic of, this type of regulator when flow nears the valve's maximum capacity. To understand this

phenomenon and to determine your maximum flow requirements, see API 2000

To select the orifice size for your valve you need to know P1 (inlet pressure). P2 (outlet pressure set point), and maximum flow in SCFH.

1. Select the row that best represents your outlet Set Pressure (P2)

2. Select the sub-row that is representative of your Inlet Pressure (P1)

3. Find the Flow rate in that sub-row that encompasses your maximum flow. Look at the orifice column heading to determine your specific orifice size.

-2-