Sensaphone, Press enter. the model 800 responds: “enter, Enter – Sensaphone 800 User Manual

Page 80

background image

Sensaphone

®

Model 800 User’s Manual

78

3. Press the number (1 to 8) of the selected temperature zone to
be calibrated.

4

MAX CALLS

5

TEMP LIMITS

6

CALIBRATE

8

CLOCK

3

INTERCALL

TIME

7

RECOGNITION

TIME

9

LISTEN TIME

SOUND

0

ID NUMBER

POWER

1

CALL

DELAY

2

VOICE

REPS

4. Enter the number required to offset the current temperature
reading so a correct reading is obtained.

• To program a positive offset number (up to +10 degrees),

enter the number on the keypad. The Model 800 recites the
digits as they are pressed.

• To program a negative offset number (up to –10 degrees),

first press *. The unit responds with “negative.” Next, enter
the number on the keypad. The unit recites the digits as they
are pressed.

4

MAX CALLS

5

TEMP LIMITS

6

CALIBRATE

8

CLOCK

3

INTERCALL

TIME

7

RECOGNITION

TIME

9

LISTEN TIME

SOUND

0

ID NUMBER

POWER

1

CALL

DELAY

2

VOICE

REPS

5. Press ENTER. The Model 800 responds:“Enter.”

ENTER

PM

NOTE

If you find that your calibration offset exceeds more
than + 5 or –5 degrees, other complicating factors
could be affecting normal operation of the Model
800. Call Sensaphone for technical assistance.