Sensaphone, Press enter. the model 800 responds: “enter, Enter – Sensaphone 800 User Manual
Page 80
Sensaphone
®
Model 800 User’s Manual
78
3. Press the number (1 to 8) of the selected temperature zone to
be calibrated.
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
8
CLOCK
3
INTERCALL
TIME
7
RECOGNITION
TIME
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
1
CALL
DELAY
2
VOICE
REPS
4. Enter the number required to offset the current temperature
reading so a correct reading is obtained.
• To program a positive offset number (up to +10 degrees),
enter the number on the keypad. The Model 800 recites the
digits as they are pressed.
• To program a negative offset number (up to –10 degrees),
first press *. The unit responds with “negative.” Next, enter
the number on the keypad. The unit recites the digits as they
are pressed.
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
8
CLOCK
3
INTERCALL
TIME
7
RECOGNITION
TIME
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
1
CALL
DELAY
2
VOICE
REPS
5. Press ENTER. The Model 800 responds:“Enter.”
ENTER
PM
NOTE
If you find that your calibration offset exceeds more
than + 5 or –5 degrees, other complicating factors
could be affecting normal operation of the Model
800. Call Sensaphone for technical assistance.