3 .4 summary of the alarm dial-out process – Sensaphone 800 User Manual

Page 40

background image

Sensaphone

®

Model 800 User’s Manual

38

Action—Response

1. THE MODEL 800 DETECTS AN

ALERT CONDITION

An alert condition is not the same as
a valid alarm—the condition must
continue for the programmed time
period, or Recognition Time, before
it is recognized as a valid alarm.

2. A VALID ALARM IS

CONFIRMED

An audible, on-site alarm message
begins and continues until the
alarm is acknowledged. (If the
Mute feature is turned on, there is
no on-site message.) Call Delay is
activated.

3. DIAL-OUT BEGINS

Dial-out begins by calling telephone
number 1 to report an alarm.
If there is no acknowledgment, the
Model 800 waits the programmed
Intercall Time before dialing
subsequent telephone numbers. Dial-
out continues in this manner, cycling
through the remaining telephone
numbers, for the programmed Max
Calls
.

4. THE ALARM IS

ACKNOWLEDGED

When the alarm is acknowledged,
the dial-out process is cancelled and
the audible, on-site alarm message
stops.

Programmable Feature

• Recognition Time

This is the programmed
waiting period to determine
if an alert condition has
persisted long enough to be
considered a valid alarm.
If the sensor returns to
normal within recognition
time, then no alarm will
occur.

• Call Delay

This is the programmed
waiting period, before the
first telephone number is
called, to report an alarm.

• Intercall Time

This is the programmed
waiting period, in between
sequential dialing of
telephone numbers, to
report an alarm.

• Max Calls

This is the total number of
telephone calls that will be
dialed in response to any
valid alarm. Telephone
numbers are dialed
sequentially, and continue
to cycle until the maximum
number of calls is reached. If
no acknowledgment occurs,
then at the completion of
Max Calls, all alarms are
automatically acknowledged.

3 .4 Summary of the Alarm Dial-Out Process