8 .1 .1 To program the Output Mode:

1. Press the SET key.

SET

2. Press the OUTPUT key.

OUTPUT

PAUSE

AM

The 800 will say “Enter output mode.”

3. Using the number keys, enter a value for the output mode.

Mode Description
6

Output on when zone 6 goes into alarm. Off when alarm is

acknowledged.
7

Output on when zone 7 goes into alarm. Off when alarm is

acknowledged.

8

Output on when zone 8 goes into alarm. Off when alarm is

acknowledged.
9

Output on when a Sound alarm occurs. Off when alarm is

acknowledged.
0

Output on when a Power alarm occurs. Off when alarm is

acknowledged.
Phone Output on when phone line is unplugged for more than 15

seconds. Off when a phone line is plugged in.

*

Output on when any alarm occurs. Off when all alarms are

acknowledged.

#

Output controlled manually via keypad command or touch-

tone telephone. (default)

Code Output on when any alarm occurs, except for when a phone

line is unplugged. Off when all alarms are acknowledged.