TABLE 6 — 569J*12-14 PIPING RECOMMENDATIONS (TWO-CIRCUIT UNIT)
NOTES: 569J requires TWO sets of refrigeration piping
R-410A
EQUIVALENT LENGTH
FT
0-38
38-75
75-113
113-150
150-188
M
0-12
12-23
23-34
34-46
46-57
Model
Typ Linear ft
0-25
25-50
50-75
75-100
100-125
569J*12
Liquid Line
3
/
8
3
/
8
3
/
8
1
/
2
1
/
2
1
/
2
Max Lift
25
50
28
75
100
99
Suction Line
7
/
8
7
/
8
1
1
/
8
1
1
/
8
1
1
/
8
Charge ea. (lbs)
7.1
8.1
9.6
11.9
13.8
15.8
569J*14
Liquid Line
3
/
8
3
/
8
3
/
8
1
/
2
1
/
2
1
/
2
Max Lift
25
50
48
75
100
122
Suction Line
7
/
8
7
/
8
1
1
/
8
1
1
/
8
1
1
/
8
Charge ea. (lbs)
9.7
10.7
12.2
14.5
16.4
18.4
569J*16
Liquid Line
1
/
2
1
/
2
1
/
2
1
/
2
1
/
2
Max Lift
25
50
75
100
125
Suction Line
7
/
8
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
Charge ea. (lbs)
11.7
13.8
15.7
17.6
19.6
569J*25
Liquid Line
1
/
2
1
/
2
1
/
2
5
/
8
1
/
2
5
/
8
1
/
2
5
/
8
Max Lift
25
50
54
75
60
99
46
95
Suction Line
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
1
3
/
8
1
3
/
8
Charge (lbs)
A
B
19.3
18.3
21.0
20.3
23.0
22.0
26.0
25.0
25.9
24.9
29.7
28.7
28.0
27.0
32.7
31.7
LEGEND
Length Equiv --- Equivalent tubing length, including effects of refrigeration specialties devices
Typ Linear
--- Typical linear tubing length, Feet (50% added to linear to define Equivalent Length for this table)
Liquid Line
--- Tubing size, inches OD.
Max Lift
--- Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —
S
Linear Length Less than 100 ft: Minimum 2.0°F subcooling entering TXV
S
Linear Length Greater than 100 ft: Minimum 0.5°F subcooling entering TXV
Suction Line --- Tube size, inches OD
Charge
--- Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where
applicable)
NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact your local
Bryant representative.
569J