beautypg.com

569j – Bryant LEGACY 569J User Manual

Page 47

background image

47

569J* 07-14 PIPING RECOMMENDATIONS (SINGLE-CIRCUIT UNIT)

R-410A

EQUIVALENT LENGTH

FT

0-38

38-75

75-113

113-150

150-188

M

0-12

12-23

23-34

34-46

46-57

Model

Typ Linear ft

0-25

25-50

50-75

75-100

100-125

569J*07

Liquid Line

3

/

8

3

/

8

1

/

2

1

/

2

1

/

2

5

/

8

1

/

2

5

/

8

Max Lift

25

42

50

75

90

100

86

101

Suction Line

7

/

8

1-

1

/

8

7

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

Charge (lbs)

8.4

9.6

11.1

13.1

15.0

18.8

16.9

22.6

569J*08

Liquid Line

1

/

2

1

/

2

1

/

2

1

/

2

1

/

2

Max Lift

25

50

75

100

112

Suction Line

7

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

Charge (lbs)

11.8

9.6

12.9

16.8

18.7

569J*12

Liquid Line

1

/

2

1

/

2

1

/

2

5

/

8

1

/

2

5

/

8

1

/

2

5

/

8

Max Lift

25

50

48

73

54

87

43

84

Suction Line

1-

1

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

1-

3

/

8

1-

1

/

8

1-

3

/

8

Charge (lbs)

13.9

15.4

17.3

20.1

20.0

23.7

22.1

26.8

569J*14

Liquid Line

1

/

2

1

/

2

5

/

8

1

/

2

5

/

8

5

/

8

3

/

4

5

/

8

3

/

4

Max Lift

25

50

50

45

75

100

100

95

107

Suction Line

1-

1

/

8

1-

1

/

8

1-

3

/

8

1-

3

/

8

1-

3

/

8

Charge (lbs)

16.9

18.8

20.7

21.3

24.1

27.2

32.2

30.2

36.5

569J*16

Liquid Line

5

/

8

5

/

8

5

/

8

5

/

8

5

/

8

Max Lift

25

50

75

100

125

Suction Line

1-

1

/

8

1-

3

/

8

1-

3

/

8

1-

3

/

8

1-

3

/

8

1-

5

/

8

Charge (lbs)

24.3

27.5

30.6

33.7

37.8

569J*25

Liquid Line

5

/

8

5

/

8

5

/

8

5

/

8

5

/

8

Max Lift

25

50

71

77

63

Suction Line

1-

1

/

8

1-

3

/

8

1-

3

/

8

1-

3

/

8

1-

5

/

8

1-

5

/

8

1-

5

/

8

Charge (lbs)

37.8

40.8

44.6

47.8

51.1

LEGEND
Length Equiv --- Equivalent tubing length, including effects of refrigeration specialties devices
Typ Linear

--- Typical linear tubing length, Feet (50% added to linear to define Equivalent Length for this table)

Liquid Line

--- Tubing size, inches OD.

Max Lift

--- Maximum liquid lift (indoor unit ABOVE outdoor unit only), at maximum permitted liquid line pressure drop —

S

Linear Length Less than 100 ft: Minimum 2.0°F subcooling entering TXV

S

Linear Length Greater than 100 ft: Minimum 0.5°F subcooling entering TXV

Suction Line --- Tube size, inches OD
Charge

--- Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger suction line size (where

applicable)

NOTE: For applications with equivalent length greater than 188 ft (57 m) and/0r linear length greater than 125 ft (38 m), contact your local

Bryant representative.

569J