beautypg.com

Electrical data (cont.) – Bryant LEGACY 569J User Manual

Page 43

background image

43

ELECTRICAL DATA (cont.)

569J*14 COOLING WITHOUT POWERED CONVENIENCE OUTLET

V---Ph---Hz

VOLTAGE RANGE

COMP 1

OFM (ea)

POWER SUPPLY

MIN

MAX

RLA

LRA

WATTS

FLA

MCA

Fuse

208/230---3---60

187

253

48.1

245

325

1.5

63.1

100

460---3---60

414

506

18.6

125

325

0.8

24.8

40

575---3---60

518

633

14.7

100

325

0.6

19.6

30

569J*14 COOLING WITH POWERED CONVENIENCE OUTLET

V---Ph---Hz

VOLTAGE RANGE

COMP 1

OFM (ea)

POWER SUPPLY

MIN

MAX

RLA

LRA

WATTS

FLA

MCA

Fuse

208/230---3---60

187

253

48.1

245

325

1.5

67.9

100

460---3---60

414

506

18.6

125

325

0.8

27.0

40

575---3---60

518

633

14.7

100

325

0.6

21.3

30

569J*14 COOLING WITHOUT POWERED CONVENIENCE OUTLET

V---Ph---Hz

VOLTAGE RANGE

COMP 1

COMP 2

OFM (ea)

POWER SUPPLY

MIN

MAX

RLA

LRA

RLA

LRA

WATTS

FLA

MCA

Fuse

208/230---3---60

187

253

22.40

149

22.40

149

325

1.5

53.4

60

460---3---60

414

506

10.6

75

10.6

75

325

0.8

25.4

30

575---3---60

518

633

7.7

54

7.7

54

325

0.6

18.5

25

569J*14 COOLING WITH POWERED CONVENIENCE OUTLET

V---Ph---Hz

VOLTAGE RANGE

COMP 1

COMP 2

OFM (ea)

POWER SUPPLY

MIN

MAX

RLA

LRA

RLA

LRA

WATTS

FLA

MCA

Fuse

208/230---3---60

187

253

22.40

149

22.40

149

325

1.5

58.2

80

460---3---60

414

506

10.6

75

10.6

75

325

0.8

27.7

35

575---3---60

518

633

7.7

54

7.7

54

325

0.6

20.2

25

569J