Ahri* capacity ratings – Bryant LEGACY 569J User Manual
Page 4

4
AHRI* CAPACITY RATINGS
UNIT
COOLING
CIRCUITS
NOM.
CAPACITY
(TONS)
NET COOLING
CAPACITY
(MBH)
TOTAL POWER
(kW)
EER
IEER
569J*07/524J07
1
6
71
6.1
11.2
11.4
569J*08/524J08
1
7.5
92
8.2
11.2
11.4
569J*12/524J12
1
10
117
10.3
11.2
11.4
569J*14/524J14
1
12.5
148
13.5
11
11.2
569J*16/524J16
1
15
180
16.4
11
11.2
569J*25/524J25
1
20
240
21.6
11
11.2
UNIT
COOLING
CIRCUITS
NOM.
CAPACITY
(TONS)
NET COOLING
CAPACITY
(MBH)
TOTAL POWER
(kW)
EER
IEER
569J*12/524J12
2
10
117
10.4
11.2
11.4
569J*14/524J14
2
12.5
147
13.4
11
11.8
569J*16/524J16
2
15
180
16.4
11
11.2
569J*25/524J25
2
20
240
21.6
11
11.2
LEGEND
AHRI
--- Air---Conditioning, Heating and Refrigeration
Institute
ASHRAE --- American Society of Heating, Refrigerating
and Air Conditioning, Inc.
EER
--- Energy Efficiency Ratio
IEER
--- Integrated Energy Efficiency Ratio
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
NOTES
1. Rated in accordance with AHRI Standard 340/360---07,
as appropriate.
2. Ratings are based on:
Cooling Standard: 27_C (80_F) db, 19_C (67_F) wb
indoor air temp and 35_C (95_F) db outdoor air temp.
IEER Standard: 27_C (80_F) db, 19_C (67_F) wb indoor
air temp and 4 various outdoor temperatures.
3. All units comply with ASHRAE 90.1 Energy Standard for
minimum EER and IEER requirements.
569J