beautypg.com

Selection procedure, Controls – Bryant LEGACY 569J User Manual

Page 13

background image

13

SELECTION PROCEDURE

Combination ratings for 569J units matched with 524J

Series air handlers are in this book. If unit is used with an

air handler, use the Bryant Electronic Catalog AHU

(Air-Handling Unit) selection program to obtain combined

ratings.

I.

Determine

cooling

load,

evaporator-air

temperature, and quantity.

Given:

Total Cooling Capacity

Required (TC)

121,000 Btuh

. . . . . . . . . . . . . . . . . . .

Sensible Heat Capacity

Required (SHC)

95,000 Btuh

. . . . . . . . . . . . . . . . . . .

Compressor Type

Scroll

. . . . . . . . . . . . . . . . . . . . . . . . .

Temperature Air Entering

Condenser (Edb)

95_F

. . . . . . . . . . . . . . . . . . . . . . . . .

Temperature Air Entering

Evaporator (db/wb)

80_F db, 67_F wb

. . . . . . . . . . . .

Evaporator Air Quantity

4,000 cfm

. . . . . . . . . . . . . . . . .

External Static Pressure

0.4 in. wg

. . . . . . . . . . . . . . . . .

Length of Interconnecting

Refrigerant Piping

25 ft (Linear)

. . . . . . . . . . . . . . . . .

Power Supply (V-Ph-Hz)

208/230-3-60

. . . . . . . . . . . . .

II.

Select condensing unit air-handler combination.
For this example, select a 569J*12 matched with a

524J12 coil. This 569J*12/524J12 condensing unit

air-handler combination provides 122,000 Btuh of

total cooling capacity and 97,200 Btuh of sensible

capacity at the given conditions. If other

temperatures or airflow values are required,

interpolate the values from the combination ratings.

III. Determine sizes of liquid and suction lines.

Enter Refrigerant Piping Sizes table. The sizes

shown are based on an equivalent length of pipe.

This equivalent length is equal to the linear length

of pipe indicated at the top of each sizing column,

plus a 50% allowance for fitting losses. (For a more

accurate determination of actual equivalent length

in place of using the estimated 50% value, refer to

Bryant System Design Manual.) For this example,

note in the linear length column that the proper pipe

size is

1

/

2

in. for the liquid line and 1

3

/

8

in. for the

suction line.
For extended line lengths over 100 feet, contact

your Bryant representative or application engineer.

IV. Determine fan rpm and bhp (brake horsepower).

Refer to the 524J Air Handler Catalog -- Fan

Performance table. Enter the Air Handler Fan

Performance table at 524J12 at 4000 cfm and move

to the External Static Pressure (ESP) column. Note

that the conditions require 803 rpm at 1.77 bhp.

V.

Determine motor and drive.
Enter the Fan Motor Data tables and find the

standard motor for 524J*12 unit rated at 2.4 Hp.

Since the bhp required is 1.77, a standard motor

satisfies the requirement and should be used.
Next, find the type of drive that satisfies the 803

rpm requirement in the Drive Data tables. For the

524J*12 unit, the Standard Drive table shows an

rpm range of 666-863. Since the rpm required is

803, the standard drive satisfies the requirement and

should be used.

CONTROLS

Operating sequences

569J*07--25

At start-up, the thermostat calls for cooling. With all

safety devices satisfied, the compressor contactor and fan

contactor

energize,

causing

the

compressor

and

outdoor-fan motor to operate. Thermostat contacts

energize, allowing the field-supplied and field-installed

indoor-fan contactor to function. A field-supplied and

field-installed liquid line valve also opens, allowing the

system to function in Cooling mode. As cooling demand

is satisfied, the thermostat contacts break, de--energizing

the contactor and causing the system to shut off. The

liquid line solenoid valve closes, minimizing the potential

for refrigerant migration. The compressor does not restart

until the thermostat again calls for cooling. The system is

protected with a safety circuit so that the system will not

start if a fault exists (i.e., high or low pressure fault). To

reset the safety circuit, set the thermostat to eliminate the

cooling demand, then return it to the original setpoint.

This should be done only once, and if the system shuts

down due to the same fault, determine the problem before

attempting to restart the system.

569J