C15200 | oms: stop function, C15205 | sse: emergency stop function, C15300 | restart behaviour – Lenze E84Dxxxxx User Manual
Page 60: C15305 | ss1: stop time, C15205, C15300/1, C15305, C15310, C15200, C15201

7
Parameter reference
7.1
Parameter list | C15200
60
Lenze · 8400 protec · Drive-based safety · Software Manual · DMS 2.4 EN · 05/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C15200
C15201
C15205
C15300
C15305
C15310
Parameter | Name:
C15200 | OMS: Stop function
Data type: UNSIGNED_8
Index: 9375
d
= 249F
h
Selection of the stop function during special operation
Selection list
(read only)
Information
0 STO
1 SS1
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C15201 | C15201
Data type: UNSIGNED_8
Index: 9374
d
= 249E
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C15205 | SSE: Emergency stop function
Data type: UNSIGNED_8
Index: 9370
d
= 249A
h
Selection of the stop function for emergency stop.
Selection list
(read only)
Information
0 STO
1 SS1
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C15300 | Restart behaviour
Data type: UNSIGNED_8
Index: 9275
d
= 243B
h
Behaviour for the restart after the functions have been deactivated.
Selection list
0 Acknowledged restart
1 Automatic restart
Subcodes
Information
C15300/1
Restart - STO, SS1
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C15305 | SS1: Stop time
Data type: UNSIGNED_16
Index: 9270
d
= 2436
h
Display range
(min. value | unit | max. value)
0
ms
30000
Read access Write access CINH PLC STOP No transfer Scaling factor: 1
Parameter | Name:
C15310 | C15310
Data type: UNSIGNED_16
Index: 9265
d
= 2431
h
This code is for device-internal use only and must not be written to by the user!