2.5
Diagnostics & error management
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Error states
Detected errors or maloperation of the drive are assigned to error states with definite responses.
The response can be co-ordinated with the complete drive via the error states.
Error in PROFIsafe communication
When PROFIsafe is used as safety bus:
• If errors occur in the PROFIsafe communication, the data are passivated by the PROFIsafe driver.
• After the PROFIsafe communication is reinitialised, the drive reenabled if no standstill function
has been selected.
• Events which cause an error status are sent as a diagnostic telegram via the safety bus.
Logbook
The logbook function integrated in the controller records important events in the system in
chronological order, including error states of the drive-based safety system.
Tip!
When an online connection has been established, the logbook can be displayed in the
»Engineer« via the Logbook button on the Diagnostic tab for the controller.
Detailed information on the logbook can be found in the Online Help for the controller.
Features
Error status
System error
Fault
Warning
Event
Fatal internal error
Error
Monitoring function
LED "S_Error"
On
On
On
State of the drive-based
safety system
Lockout (CPU stopped)
Error status
Normal operation
The control category
according to EN 954-1...
... has been abandoned
... has not been abandoned
Response
The motor is immediately
safely switched to torqueless
operation via
• STO
The motor is immediately safely switched to torqueless
operation via
• STO
or shutdown via
• SS1 (parameterisable)
Acknowledgement after
event has been
eliminated
• Switching off and then on
again of the 24-V supply at
the safety module
• Error acknowledgement (AIE) plug X62 (positive
signal pulse with a signal duration of 0.3 ... 10 s)
• Error acknowledgement (AIE) via safety bus (bit
"PS_AIE")
• Switching off and then on again of the 24-V supply
at the safety module
Note!
If the system error still occurs after switching the supply voltage, please contact the
Lenze service!