Lenze−Codestellen und CANopen−Objekte
Description of the codes relevant for CAN
l
49
EDSMF2181IB EN 3.0
C0351:
Set baud rate
Code
C0351
Name
CAN baud rate
Index: 0x5EA0 (24224)
Subcode
Lenze
Values
Access
Data type
−
0
0
500 kbit/s
rw
I32
1
250 kbit/s
2
125 kbit/s
3
50 kbit/s
4
1000 kbps
5
20000 kbps
16
Automatic detection
¨ RSP þ PS transfer
¨ CANopen:
The baud rate over the CAN bus can be set using this code.
Changes to the setting are applied after:
ƒ
Reconnection to the mains
ƒ
A "reset node" command via the bus system
ƒ
A reset node using the code C0358
Prior to accessing the CAN bus, the baud rate used is determined by the communication
module and compared with the baud rate configured.
If the two values are different, the baud rate determined is used. The baud rate detected
by the communication module can be read using code C1209.
If there is no data traffic on the CAN bus, the baud rate cannot be determined. The
subsequent behaviour of the communication module depends on the selection configured
in code C0351:
ƒ
Selection 0 ... 5
After a time−out that can be configured using code C1215, the CAN bus is accessed
with the baud rate configured.
ƒ
Selection 16 (automatic detection of the baud rate)
The communication module does not access the bus until a baud rate can be
detected.