Connection for the can bus, Installation, Electrical installation connection for the can bus – Lenze EMF2181IB User Manual

Page 24: 5 connection for the can bus, Assignment of the sub−d plug connector

background image

Installation

Electrical installation
Connection for the CAN bus

5

l

24

EDSMF2181IB EN 3.0

5.2.5

Connection for the CAN bus

2181FEW001K

Assignment of the Sub−D plug connector

View

Pin

Assignment

1

6

5

9

1, 4, 5, 6, 8, 9

2

CAN−LO

3

CAN−GND

7

CAN−HI

Between CAN_LOW and CAN−HIGH the CAN bus has to be terminated by resistors (120

W).

The Sub−D plug with an integrated terminating resistor (order no. EWZ0046, not included
in the scope of supply) complies with the recommendation DS 102−1 of CiA.

L

EW

Z0046

OF

F

ON

OFF

ON

ON

OFF

р

р

р

р

OUT

IN

IN

IN

On

Off

On

120

120

120

L

EWZ0046

L

EWZ0046

L

EWZ0046

2181FEW004

Specification of the transmission cable

We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W (95 ... 140 W)

Cable resistance/cross−section

Cable length

£ 300 m £ 70 mW/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£ 40 mW/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£ 5 ns/m