Electrical installation
Connection for the CAN bus
l
27
EDSMF2181IB EN 3.0
Check repeater application
Given:
l
Baud rate:
125 kbit/s
l
Cable cross−section:
0.5 mm
2
l
Number of nodes:
28
l
Cable length:
450 m
Test sequence
Cable length
See
1. Total cable length at 125 kbit/s:
630 m
2. Segment cable length for 28 nodes and a cable cross−section of
0.5 mm
2
:
360 m
3. Comparison: The value under point 2 is smaller than the required cable length of 450 m.
Conclusion
l
It is not possible to use a cable length of 450 m without installing a repeater.
l
After 360 m (point 2) a repeater must be installed.
Result
l
The Lenze repeater, type 2176 (cable reduction: 30 m), is used.
l
Calculation of the max. cable length:
First segment: 360 m
Second segment: 360 m (according to Tab. 5−1) minus 30 m (cable reduction when a repeater is used)
à
Max. possible cable length with repeater: 690 m.
à
Now the required cable length is possible.
)