C13861 | bus status, C13862 | bus counter, C13882 – Lenze E84DGFCR User Manual
Page 78: Is t, No_data_exchange" status (see, C13861, Communication manual 8400 motec profinet

Communication manual 8400 motec PROFINET
Parameter reference
Parameters relevant for PROFINET communication
78
L
EDS84DMOTPNET EN 2.0 - 11/2011
C13861
C13862
Parameter | Name:
C13861 | Bus status
Data type: BITFIELD_16
Index: 10714
d
= 29DA
h
Bit-coded display of current bus status
Value is bit-coded:
Bit 0 Initialised
Bit 1 Online
Bit 2 Connected
Bit 3 Address conflict
Bit 4 Hardware error
Bit 5 EEPROM error
Bit 6 Watchdog error
Bit 7 Protocol error
Bit 8 Profinet stack ok
Bit 9 Profinet stack not configured
Bit 10 Ethernet controller error
Bit 11 UDP stack error
Bit 12 Reserved
... ...
Bit 15 Reserved
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13862 | Bus counter
Data type: UNSIGNED_32
Index: 10713
d
= 29D9
h
Display of data cycles per second (irrespective of data changes)
Display area
(min. value | unit | max. value)
0
4294967295
Subcodes
Info
C13862/1
Data cycles per second
C13862/2
Read cycles per second
C13862/3
Write cycles per second
;
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT