Communication manual 8400 motec PROFINET
Commissioning
Setting the IP configuration
6.4.2
Setting via codes in the »Engineer«
You can also set the IP parameters manually via code in the »Engineer« under the Settings
tab.
The IP parameters are written to codes
(IP address),
(subnet mask), and
(gateway address).
How to activate changed settings in the »Engineer«:
1. Execute device command C00002 = "11: Save all parameter sets".
2. Carry out a "reset node" of the node, or switch the voltage supply of the
Communication Unit off and on again
Decimal representation of the IP parameters
By clicking the [ int ] buttons on the right next to the input fields, the IP parameters are
represented as decimal values.
In the case of the decimal representation, the byte sequence is inverted.
Example: IP address 192.168.0.1
= 16820416 [00000001.00000000.10101000.11000000
bin
]
Note!
• The IP address must only be allocated manually in the »Engineer« if the
PROFINET network is not actuated on the IO controller yet (IP address was not
allocated by the IO controller yet).
• During the IP parameters are set in the »Engineer«, PROFINET communication
with the IO controller must not take place at the same time.
Byte 3
Byte 2
Byte 1
Byte 0
1
0
168
192
0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 1 0 1 0 1 0 0 0 1 1 0 0 0 0 0 0