4 error information (error), Error information (error), Communication manual 8400 motec profinet – Lenze E84DGFCR User Manual
Page 59: Parameter data transfer error information (error)

EDS84DMOTPNET EN 2.0 - 11/2011
L
59
Communication manual 8400 motec PROFINET
Parameter data transfer
Error information (error)
9.4
Error information (error)
Error code
Meaning
Description
Additional
information
0x0000
Impermissible parameter
number
Access to non-available parameter
-
0x0001
Parameter value cannot be
changed
Change access to a parameter value that cannot be
changed
Subindex
0x0002
Lower or upper value limit
exceeded
Change access with value beyond the value limits
Subindex
0x0003
Faulty subindex
Access to non-available subindex
Subindex
0x0004
No array
Access with subindex to non-indicated parameter
-
0x0005
Wrong data type
Change access with value that does not go with the
data type of the parameter
-
0x0006
No setting permitted (only
resettable)
Change access with a non-zero value, where it is not
permitted.
Subindex
0x0007
Description element cannot
be changed
Change access to a description element that cannot
be changed
Subindex
0x0008
Reserved
(PROFIdrive profile V2: PPO-Write requested in IR is
not available)
-
0x0009
Description data is not
available
Access to non-available description (parameter value
is available)
-
0x000A
Reserved
(PROFIdrive profile V2: Wrong access group)
-
0x000B
No parameter change rights Change access if the parameter change rights are
missing
-
0x000C
Reserved
(PROFIdrive profile V2: Password is wrong)
-
0x000D
Reserved
(PROFIdrive profile V2: Text in the cyclic traffic
cannot be read)
-
0x000E
Reserved
(PROFIdrive profile V2: Name in the cyclic traffic
cannot be read)
-
0x000F
No text array available
Access to unavailable text array (parameter value is
available)
-
0x0010
Reserved
(PROFIdrive profile V2: PPO-Write is missing)
-
0x0011
Job cannot be executed due
to operating status
Access is not possible for temporary reasons that are
not specified in detail
-
0x0012
Reserved
(PROFIdrive-Profil V2: Other error)
-
0x0013
Reserved
(PROFIdrive profile V2: date in the cyclic traffic
cannot be read)
-
0x0014
Impermissible value
Change access with a value that is within the value
limits but is not permissible for other permanent
reasons (parameter with defined single values)
Subindex
0x0015
Response is too long
The length of the current response exceeds the
maximally transferrable length
-
0x0016
Impermissible parameter
address
Impermissible value or value which is not supported
for the attribute, number of subindexes, parameter
number, or subindex, or a combination
-
0x0017
Impermissible format
Write request: Impermissible parameter data format
or parameter data format which is not supported
-
0x0018
Number of values are not
consistent
Write request: Number of parameter data values
does not match the number of subindexes in the
parameter address
-