3 setting the station name, Setting the station name, Communication manual 8400 motec profinet – Lenze E84DGFCR User Manual
Page 28

Communication manual 8400 motec PROFINET
Commissioning
Setting the station name
28
L
EDS84DMOTPNET EN 2.0 - 11/2011
6.3
Setting the station name
The station name currently used is shown in code
.
The station name ...
is required for unambiguous addressing of the Inverter Drive 8400 motec by the I/O
controller.
can either be assigned by the I/O controller via PROFINET or set manually in the
»Engineer«.
has to be allocated in accordance with the PROFINET specification:
– 1 or several labels separated by ".".
– Max. length per label: 63 characters
– Max. total length: 240 characters
– Permissible characters: [a ... z], [0 ... 9], [.], [-]
– Labels must not begin or end with [-].
Prohibited syntax:
– "n.n.n.n" (n = 0 ... 999)
– "port-xyz" (x, y, z = 0 ... 9)
– "port-xyz-abcde" (a, b, c, d, e, x, y, z = 0 ... 9)
Note!
• The "Node blinking test" PROFINET function which serves to identify an
accessible device is supported. The red LED BE (
flickers during execution.
• Operation on the PROFINET requires a valid station name.
• In the case of impermissible settings, the red LED BE blinks (
is output. The Communication Unit then internally
continues to work with the deleted name.
• If the station name is assigned by the IO controller via PROFINET or the
PROFINET configurator of the »Engineer«, changes will be effective
immediately.