2 possible causes and remedies, Profinet: exist. conn. to 8400 lost [0x01bc3100, Profinet: memory: no access [0x01bc5531 – Lenze E84DGFCR User Manual
Page 69: Profinet: memory: read error [0x01bc5532, Profinet: memory: write error [0x01bc5533, Profinet: restart by watchdog reset [0x01bc6010, Possible causes and remedies, 0x01bc3100, 0x01bc5531, 0x01bc5532

EDS84DMOTPNET EN 2.0 - 11/2011
L
69
Communication manual 8400 motec PROFINET
Error messages
Possible causes and remedies
12.2
Possible causes and remedies
This chapter contains all PROFINET error messages in numerical order of the error number.
Possible causes and remedies as well as responses to the error messages are described in
detail.
Short overview of the PROFINET error messages
PROFINET: Exist. conn. to 8400 lost [0x01bc3100]
PROFINET: Memory: No access [0x01bc5531]
PROFINET: Memory: Read error [0x01bc5532]
PROFINET: Memory: Write error [0x01bc5533]
PROFINET: Restart by watchdog reset [0x01bc6010]
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
;
None System fault : Fault Trouble Quick stop by trouble ; Warning locked Warning Information
Cause
Remedy
Internal communication to the Control Unit has been
interrupted.
• Inverter Drive 8400 motec has been switched off.
• Incorrect wiring of Communication Unit.
• Switch on Inverter Drive 8400 motec.
• Check Communication Unit for correct wiring.
• Send device with error description to Lenze.
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
;
None System fault : Fault Trouble Quick stop by trouble ; Warning locked Warning Information
Cause
Remedy
Access to memory was not possible.
Send device with error description to Lenze.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Parameter could not be read.
• Download application again (including module).
• Send device with error description to Lenze.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Parameter could not be written.
• Download application again (including module).
• Send device with error description to Lenze.
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
;
None System fault : Fault Trouble Quick stop by trouble ; Warning locked Warning Information
Cause
Remedy
Device is damaged.
Send device with error description to Lenze.