Profinet: data output status bad [0x01bc6503, Profinet: data_exchange status quit [0x01bc6531, Profinet: station name error [0x01bc6532 – Lenze E84DGFCR User Manual
Page 71: Profinet: ip address error [0x01bc6533, Message, 0x01bc6501, 0x01bc6502, 0x01bc6503, 0x01bc6531, 0x01bc6532

EDS84DMOTPNET EN 2.0 - 11/2011
L
71
Communication manual 8400 motec PROFINET
Error messages
Possible causes and remedies
PROFINET: Record Parameter: Invalid read [0x01bc6501]
PROFINET: Record Parameter: Invalid write [0x01bc6502]
PROFINET: Data output status bad [0x01bc6503]
PROFINET: Data_Exchange status quit [0x01bc6531]
PROFINET: Station name error [0x01bc6532]
PROFINET: IP address error [0x01bc6533]
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause
Remedy
Invalid parameter read access
Check configuration.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause
Remedy
Invalid parameter write access
When reading back data, the IO controller requested a
too short data length (number of data bytes).
Check configuration.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble : Warning locked Warning Information
Cause
Remedy
• Output data invalid.
• Connection to Siemens S7 has been interrupted.
• Check cables and terminals.
• Connect network cable to PROFINET connections.
Response (Lenze setting printed in bold)
Setting:
(; Adjustable response)
:
None System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause
Remedy
The data exchange via PROFINET has been terminated.
• See also chapter "
• Check cables and terminals.
• Connect network cable to PROFINET connections.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Station name is not DNS-conform.
Use DNS-conform station name.
Setting the station name ( 28)
Response (Lenze setting printed in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
An invalid IP address has been assigned by the I/O
controller via PROFINET or has been set in code
.
• Make sure that the I/O controller has assigned a valid
IP address via PROFINET.
• Set a valid IP address.