12 error messages, 1 short overview of the profinet error messages, Error messages – Lenze E84DGFCR User Manual
Page 68: Short overview of the profinet error messages, Communication manual 8400 motec profinet

Communication manual 8400 motec PROFINET
Error messages
Short overview of the PROFINET error messages
68
L
EDS84DMOTPNET EN 2.0 - 11/2011
12
Error messages
This chapter complements the error list in the software manual and the »Engineer« online
help for the Inverter Drive 8400 motec by PROFINET error messages.
12.1
Short overview of the PROFINET error messages
The following table contains all PROFINET error messages in numerical order of the error
number. Furthermore the preset error response and - if applicable – the parameter for
setting the error response is specified.
Tip!
When you click the cross-reference in the first column, you will get to the detailed
description (causes and remedies) of the corresponding error message.
Software manual/»Engineer« online help for the "Inverter Drive 8400 motec"
General information on diagnostics & fault analysis and error messages is
provided here.
Error no.
[hex]
Subject area
no.
[dec]
Error no.
[dec]
Error text
Error type
(Error response)
Can be set in
444
12544
PROFINET: Exist. connect. to 8400 lost
1: Error
444
21809
PROFINET: Memory: No access
1: Error
444
21810
PROFINET: Memory: Read error
1: Error
-
444
21811
PROFINET: Memory: Write error
1: Error
-
444
24592
PROFINET: Restart by watchdog reset
1: Error
444
24593
PROFINET: Internal error
1: Error
444
24832
PROFINET: Internal error
1: Error
444
24833
PROFINET: Internal error
1: Error
444
25631
PROFINET: Invalid parameter set
1: Error
444
25632
PROFINET: Error: Lenze setting loaded
1: Error
-
444
25648
PROFINET: Invalid module configuration
1: Error
444
25857
PROFINET: Record parameter: Invalid read
4: Warning locked
-
444
25858
PROFINET: Record parameter: Invalid write
4: Warning locked
-
444
25859
PROFINET: Data output status bad
4: Warning locked
-
444
25905
PROFINET: Data_Exchange status quit
0: None
444
25906
PROFINET: Station name error
1: Error
-
444
25907
PROFINET: IIP address error
1: Error
-
444
25908
PROFINET: Stack init error
1: Error
-
444
26192
PROFINET: Internal error
1: Error
-