Page 27

EDS84DMOTPNET EN 2.0 - 11/2011
L
27
Communication manual 8400 motec PROFINET
Commissioning
Configuring the PROFINET IO controller
6.2
Configuring the PROFINET IO controller
For communication with the PROFINET Communication Unit, the IO controller must be
configured first.
Configuration for device control
For the configuration of PROFINET, the current PROFINET device description file (XML) of
the Communication Unit has to be imported in the IO controller.
The device description file GSDML-Vx.z-Lenze-8440PNabb-yyyymmdd.xml can be found in
the download area at:
Defining the user data length
The user data length is defined during the initialisation phase of the I/O controller.
The PROFINET Communication Unit supports the configuration of max. 8 process data
words (max. 16 bytes).
Description of the device data base file
Example of device data base file selection
"PCD (8W)" = 8 process data words in slot 1 of the PROFINET telegram
Wildcards in the file name "GSDML-Vx.z-Lenze-8440PN100-yyyymmdd.xml"
x
Main version of the GSDML scheme used
z
Subversion of the GSDML scheme used
A
Major version of the software version
bb
Minor version of the software version
yyyy
Year
mm
Month
dd
Day
Selection text
Process data
Assigned
I/O memory
Slot 1: PCD (nW)
1 ... 8 words
0 ... 16 bytes
Slot 2: AI/DI (nW)
0 ... 2 words
0 ... 4 bytes