C13880
C13881
C13885
Parameter | Name:
C13880 | Reaction on communication failure
Data type: UNSIGNED_8
Index: 10695
d
= 29C7
h
Monitoring response in case of a communication fault
A change in the monitoring response becomes effective immediately.
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information
Subcodes
Lenze setting
Information
C13880/1
0: No response
Response to interrupted INTERBUS communication
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13881 | Monitoring time for Interbus communication failure
Data type: UNSIGNED_16
Index: 10694
d
= 29C6
h
If the "IBS-ACTIVE" status (INTERBUS is active and data are cyclically exchanged) is quit, the response parameterised
in
is executed after the monitoring time set for the data exchange has elapsed.
• The value "65535" in this code deactivates monitoring.
• A change in monitoring is effective immediately.
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
65535 65535 ms
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Delete process data
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
Setting of the process data which the controller is to process further for maintaining internal communication when
the INTERBUS has failed.
Selection list
(Lenze setting printed in bold)
0 Use of the last master process data
1 Process data are set to the value '0'
;
Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT