beautypg.com

7 data transfer, Data transfer – Lenze E84AYCIB User Manual

Page 40

background image

E84AYCIB communication manual (INTERBUS)

Data transfer

40

L

EDS84AYCIB EN 4.0 - 11/2010

7

Data transfer

The INTERBUS master and controller communicate with each other by exchanging data

telegrams via INTERBUS. The user data area of the data telegram contains parameter data

or process data. In the controller, the parameter data and process data are assigned to

different communication channels.

Communication channels

 The process data channel transmits process data.

– The process data are used to actuate the controller.
– The host (master) can directly access the process data. In the PLC, for instance, the

data are directly assigned to the I/O area.

– Process data are not saved in the controller.
– Process data are transmitted cyclically between the host and the controllers

(permanent exchange of current input and output data).

– Process data for instance are setpoints, actual values, control words, and status

words.

– In the case of Inverter Drives 8400 a maximum of 16 process data words (16 bits/

word) can be exchanged for each direction.

 The parameter data channel transmits parameter data.

– The parameter data channel provides access to all Lenze codes.
– The transmission of parameter data usually is not time-critical.
– Parameter data for instance are operating parameters, motor data, and diagnostics

information.

– The parameter changes must be stored via code C00002 of the Inverter Drive 8400.
– The parameter data channel assigns up to 4 words of the input and output data

words in the master and is structured identically for both transmission directions.

Note!

Observe the direction of the flow of information!
• Process input data (Rx data):

– Process data from the controller (slave) to the master

• Process output data (Tx data):

– Process data from the master to the controller (slave)