4 technical data, 1 general data and operating conditions, Technical data – Lenze E84AYCIB User Manual
Page 17: General data and operating conditions, E84aycib communication manual (interbus), 4technical data

EDS84AYCIB EN 4.0 - 11/2010
L
17
E84AYCIB communication manual (INTERBUS)
Technical data
General data and operating conditions
4
Technical data
4.1
General data and operating conditions
"Inverter Drives 8400" hardware manual
This manual contains data on the ambient conditions and the electromagnetic
compatibility (EMC) that also apply to the communication module.
Field
Values
Order designation
• E84AYCIBV (coated version)
• E84AYCIBS: (standard version)
Communication profile
INTERBUS
Interfaces
• Input (IN): 9-pole Sub-D plug
• Output (OUT): 9-pole Sub-D socket
Communication medium
RS485
Network topology
Ring
Type of node
INTERBUS slave
Number of nodes
• 1 master
• 512 slaves
Baud rate
500 kbps or 2 Mbps
(can be set via DIP switch or code)
Max. cable length
• 400 m at 500 kbps
• 150 m at 2 Mbps
(between the individual INTERBUS nodes)
Process data words (PD) to be used
0 ... 10: 16 bits/word
(can be set via DIP switch or code)
Parameter data words (PCP)
0, 1, 2, 4: 16 bits/word
(can be set via DIP switch or code)
Max. number of data words
10 (PD + PCP): 16 bits/word
Max. PDU length
64 bytes
INTERBUS identification (module ID) • 3 = 0x3 (PCP 0 words)
• 227 = 0xE3 (PCP 1 word)
• 224 = 0xE0 (PCP 2 words)
• 225 = 0xE1 (PCP 4 words)
Voltage supply
External supply via the 2-pole plug connector
• "+": U = 24 V DC (21.6 V - 0 % … 26.4 V + 0 %), I
max
= 180 mA
• "-": Reference potential for external voltage supply
Conformities, approvals
CE