beautypg.com

2 fieldbus status displays, Fieldbus status displays, Fieldbus status displays ( 56) – Lenze E84AYCIB User Manual

Page 56: E84aycib communication manual (interbus)

background image

E84AYCIB communication manual (INTERBUS)

Diagnostics

LED status displays

56

L

EDS84AYCIB EN 4.0 - 11/2010

11.1.2

Fieldbus status displays

The LEDs BS and BE display the fieldbus status.

E84YCIB006

LED

Colour

Status

Description

BS

Green

Off

The communication module is not active on the fieldbus.

Data cycles are not executed.

Blinking

Communication has been established via the communication

module. The INTERBUS is active. Data cycles are executed.

BE

Red

On

INTERBUS communication is interrupted.

Data cycles are not executed.

Blinking

Impermissible setting:

• Data word sum (PD + PCP) > 10

• Data word sum (PD + PCP) = 0

The communication module has been initialised and continues to

operate internally with the following values:

• PD = 2 (words)

• PCP = 1 (word)

BE

BS

200 ms

200 ms

200 ms

200 ms