6 external voltage supply, External voltage supply, External voltage supply ( 31) – Lenze E84AYCIB User Manual
Page 31
EDS84AYCIB EN 4.0 - 11/2010
L
31
E84AYCIB communication manual (INTERBUS)
Installation
Electrical installation
5.2.6
External voltage supply
The communication module can be supplied externally with voltage via separate supply
cables at the 2-pole plug connector (X205).
External voltage supply of the communication module is necessary if the bus
communication is to continue when the supply of the standard device fails.
It is not possible to access the parameters of a standard device that is disconnected
from the mains.
Wiring the X205 plug connector
[5-6]
Wiring of the 2-pole plug connector with spring connection
How to wire the plug connector with spring connection:
1. Place a screwdriver into the notch below the terminal and keep it pressed.
2. Place the supply cable in the terminal.
3. Remove the screwdriver from the notch.
Note!
With external voltage supply, always use a separate power supply unit, safely
separated in accordance with EN 61800-5-1 in every control cabinet ("SELV" /
"PELV").
Stop!
Only wire the plug connector if the standard device is disconnected from the
mains.
E84AYCXX010