Invalid module configuration [0x01bc6430, Invalid configuration [0x01bc8125, Communication stack reset [0x01bc8126 – Lenze E84AYCIB User Manual
Page 62: Invalid initialisation [0x01bc8127, Data exchange stopped [0x01bc8131, 0x01bc8126, 0x01bc8131, 0x01bc8125, 0x01bc8127, 0x01bc6430
E84AYCIB communication manual (INTERBUS)
Error messages
Possible causes and remedies
62
L
EDS84AYCIB EN 4.0 - 11/2010
Invalid module configuration [0x01bc6430]
Invalid configuration [0x01bc8125]
Communication stack reset [0x01bc8126]
Invalid initialisation [0x01bc8127]
Data exchange stopped [0x01bc8131]
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Module configuration is faulty.
Check and correct module configuration.
Response (Lenze setting in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked : Warning Information
Cause
Remedy
The active configuration is invalid:
• Data word sum (PD + PCP) > 10 words
• Data word sum (PD + PCP) = 0
Adapt the number of PD and PCP:
• Data word sum (PD + PCP) = 1 ... 10 words
Response (Lenze setting in bold)
Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Error during processing the INTERBUS services
Execute reinitialisation by the master.
Response (Lenze setting in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked : Warning Information
Cause
Remedy
The INTERBUS initialisation has failed.
Execute reinitialisation by the master.
Response (Lenze setting in bold)
Setting:
:
None System fault : Fault Trouble : Quick stop by trouble : Warning locked Warning : Information
Cause
Remedy
The data exchange at the INTERBUS has been
terminated.
• Check cables and connections.
• Execute reinitialisation by the master.